Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for distribution
circuits, and for feeders or branch circuits. Type MV cables may be installed in wet or
dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground
duct, directly buried if installed in a system with a grounding conductor in close
proximity that conforms with NEC Section 250-51, or messenger supported in industrial
establishments and electric utilities.
Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.
Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds
electrical and physical requirements of ICEA S-93-639/NEMA WC74 &
S-97-682, AEIC CS8 and UL 1072.
Insulation: Meets or exceeds electrical and physical requirements of ICEA
S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.
Insulation Screen: Extruded semiconducting EPR insulation screen. Meets or
exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74
& S-97-682, AEIC CS8 and UL 1072.
Shield: 5 mil bare copper tape helically applied.
Jacket: Meets or exceeds electrical and physical requirements of ICEA
S-93-639/NEMA WC74 & S-97-682 and UL1072 for polyvinyl chloride jackets.
UL Listed as Type MV-105 and sunlight resistant, in accordance with UL
1072.
A flame retardant construction, size 1/0 AWG and larger, for installation in cable tray
is available on special order. This construction is UL labeled "MV-105 FOR CT
USE."
Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized
industry standards (UL, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating
temperature. 140°C emergency rating. 250°C short circuit rating. Excellent corona
resistance. Screens are clean stripping. Exceptional resistance to "treeing."
Moisture resistant. Resistant to most oils, acids, and alkalies. Sunlight resistant.
Improved Temperature Rating. |