COMPACT STRAND CONSTRUCTION |
Product Data
Section 2: Sheet 11 |
Okoguard®-Okolon®
Type MV-105
15kV Shielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor/105°C Rating
100% and 133% Insulation Level
|
A Uncoated, Okopact (Compact Stranded) Copper Conductor B Strand Screen-Extruded Semiconducting EPR
C Insulation-Okoguard EPR
D Insulation Screen-Extruded Semiconducting EPR
E Shield-Coated Copper Tape
F Jacket-Okolon
Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene (EPR)
based, thermosetting compound, whose optimum balance of electrical and physical properties
is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red
color and a totally integrated EPR system, provides the optimum balance of electrical and
physical properties for long, problem free service.
The triple tandem extrusion of the screens with the insulation provides optimum
electrical characteristics.
Jacket
The Okolon jacket on this cable is a vulcanized chlorosulfonated polyethylene base
compound which is mechanically rugged, flame, radiation, and oil resistant. |
Applications
Okoguard shielded Okolon Type MV-105 power cables are recommended for use as feeder
circuits in electric utility generating stations, for distribution circuits, and for
feeders or branch circuits in industrial and commercial installations. Type MV cables may
be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any
raceway or underground duct, directly buried if installed in a system with a grounding
conductor in close proximity that conforms with NEC Section 250-51, or messenger supported
in industrial establishments and electric utilities. Sizes 1/0 AWG and larger may also be
installed in cable tray. Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.
Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds
electrical and physical requirements of ICEA S-93-639/NEMA WC74 &
S-97-682, AEIC CS8, CSA C68.3 and UL 1072.
Insulation: Meets or exceeds electrical and physical requirements of ICEA
S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.
Insulation Screen: Extruded semiconducting EPR insulation screen. Meets or
exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74
& S-97-682, AEIC CS8, CSA C68.3 and UL 1072.
Shield: 5 mil coated copper tape helically applied, 25% lap.
Jacket: Meets or exceeds electrical and physical requirements of ICEA
S-93-639/NEMA WC74 & S-97-682, CSA C68.3 and UL 1072 for chlorosulfonated polyethylene jackets.
UL Listed as Type MV-105, sunlight resistant and for use in cable tray in
accordance with UL 1072.
CSA listed meeting the requirements of C68.3 and rated FT4 (1/0
AWG and larger) and -25°C.
Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized
industry standards (UL, CSA, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating temperature.
140°C emergency rating. 250°C short circuit rating. Passes UL and IEEE 383 and 1202 (1/0
AWG & larger) Vertical Tray Flame Tests. Excellent corona resistance. Radiation
resistant. Screens are clean stripping. Exceptional resistance to "treeing".
Moisture resistant. Resistant to most oils, acids, and alkalies. Sunlight resistant.
Improved Temperature Rating. |
1-Catalog Number(1)
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
|
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(2)
13-Ampacities Underground Duct(3)
14-Ampacities Cable Tray(4)
15-Conduit Size-Inches*(5)
|
| 1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
10 |
11 |
12 |
13 |
14 |
15 |
| Okoguard Insulation:175 mils(4.45mm), 100% Insulation Level |
115-23-2011 |
2 |
33.6 |
0.66 |
0.72 |
80 |
2.03 |
0.97 |
24.5 |
625 |
735 |
165 |
165 |
- |
3 |
115-23-2013 |
1 |
42.4 |
0.69 |
0.75 |
80 |
2.03 |
1.00 |
25.3 |
700 |
805 |
190 |
185 |
- |
3 |
115-23-2015 |
1/0 |
53.5 |
0.73 |
0.79 |
80 |
2.03 |
1.04 |
26.3 |
790 |
900 |
215 |
215 |
220 |
3 |
115-23-2017 |
2/0 |
67.4 |
0.77 |
0.83 |
80 |
2.03 |
1.07 |
27.2 |
900 |
1010 |
255 |
245 |
250 |
3 |
115-23-2019 |
3/0 |
85.0 |
0.82 |
0.88 |
80 |
2.03 |
1.12 |
28.5 |
1040 |
1150 |
290 |
275 |
290 |
3 1/2 |
115-23-2021 |
4/0 |
107.0 |
0.87 |
0.93 |
80 |
2.03 |
1.18 |
29.8 |
1210 |
1335 |
330 |
315 |
335 |
3 1/2 |
115-23-2023 |
250 |
127.0 |
0.91 |
0.97 |
80 |
2.03 |
1.22 |
30.9 |
1360 |
1485 |
365 |
345 |
370 |
3 1/2 |
115-23-2027 |
350 |
177.0 |
1.01 |
1.07 |
80 |
2.03 |
1.32 |
33.5 |
1730 |
1880 |
440 |
415 |
460 |
4 |
115-23-2031 |
500 |
253.0 |
1.13 |
1.21 |
80 |
2.03 |
1.45 |
36.9 |
2290 |
2505 |
535 |
500 |
575 |
4 |
115-23-2035 |
750 |
380.0 |
1.31 |
1.39 |
80 |
2.03 |
1.64 |
41.5 |
3185 |
3590 |
655 |
610 |
745 |
5 |
115-23-2038 |
1000 |
507.0 |
1.47 |
1.55 |
110 |
2.79 |
1.81 |
46.0 |
4155 |
4600 |
755 |
690 |
890 |
5 |
| Okoguard Insulation:220 mils(5.59mm), 133% Insulation Level |
115-23-2111 |
2 |
33.6 |
0.75 |
0.81 |
80 |
2.03 |
1.06 |
26.9 |
715 |
825 |
165 |
165 |
- |
3 |
115-23-2113 |
1 |
42.4 |
0.78 |
0.84 |
80 |
2.03 |
1.09 |
27.7 |
790 |
840 |
190 |
185 |
- |
3 |
115-23-2115 |
1/0 |
53.5 |
0.82 |
0.88 |
80 |
2.03 |
1.13 |
28.6 |
885 |
995 |
215 |
215 |
220 |
3 1/2 |
115-23-2117 |
2/0 |
67.4 |
0.86 |
0.92 |
80 |
2.03 |
1.17 |
29.6 |
1000 |
1125 |
255 |
245 |
250 |
3 1/2 |
115-23-2119 |
3/0 |
85.0 |
0.91 |
0.97 |
80 |
2.03 |
1.22 |
30.9 |
1140 |
1270 |
290 |
275 |
290 |
3 1/2 |
115-23-2121 |
4/0 |
107.0 |
0.96 |
1.02 |
80 |
2.03 |
1.27 |
32.2 |
1315 |
1460 |
330 |
315 |
335 |
3 1/2 |
115-23-2123 |
250 |
127.0 |
1.07 |
1.12 |
80 |
2.03 |
1.30 |
33.3 |
1465 |
1620 |
365 |
345 |
370 |
4 |
115-23-2127 |
350 |
177.0 |
1.11 |
1.18 |
80 |
2.03 |
1.43 |
36.3 |
1890 |
2085 |
440 |
415 |
460 |
4 |
115-23-2131 |
500 |
253.0 |
1.22 |
1.30 |
80 |
2.03 |
1.55 |
39.3 |
2415 |
2630 |
535 |
500 |
575 |
5 |
115-23-2135 |
750 |
380.0 |
1.40 |
1.49 |
80 |
2.03 |
1.68 |
42.7 |
3289 |
3584 |
655 |
610 |
745 |
5 |
115-23-2138 |
1000 |
507.0 |
1.56 |
1.66 |
110 |
2.79 |
1.92 |
48.9 |
4355 |
4800 |
755 |
690 |
890 |
6 |
115-23-2144 |
1250 |
633.5 |
1.75 |
1.85 |
110 |
4.33 |
2.13 |
53.4 |
5400 |
5700 |
845 |
770 |
995 |
6 |
115-23-2145 |
1500 |
760.2 |
1.90 |
1.98 |
110 |
4.33 |
2.25 |
57.1 |
6250 |
6800 |
925 |
845 |
1090 |
6 |
Authorized Stock Item.
Available from our Customer Service Centers. Minimum Manufacturing Quantity for
non-stock items is 5000'.
Aluminum Okopact Conductors
(1) Aluminum Okopact conductors are available on special order. To
order aluminum Okopact conductors, change the first three digits of the catalog number
from 115 to 135.
Ampacities
(2) Ampacities are in accordance with Table 310-73 of the NEC for
three single Type MV-105 conductors, or single conductors twisted together (triplexed) and
installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor
temperature of 105°C.
(3) Ampacities are in accordance with Table 310-77 of the NEC for
three single conductors or triplexed cable in one underground raceway, three feet deep
with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of
20°C and thermal resistance (RHO) of 90.
(4) Ampacities based on single Type MV-105 conductors, or single
conductors twisted together (triplexed, quadruplexed, etc.), size1/0 AWG and larger,
installed in uncovered cable tray in accordance with Section 318-13 of the NEC at an
ambient temperature of 40°C and a conductor temperature rating of 105°C. In accordance
with NEC Section 318-13(b), the ampacities are 75% of the values given in NEC Table 310-69
(copper conductors). Where the cable tray is covered for more than six feet with solid
unventilated covers, the ampacities shall not exceed 93% of the values shown above.
Refer to the NEC, IEEE/ICEA-S-135 Power Cable Ampacities, or the Okonite Engineering
Data Bulletin for installation in duct banks, multiple point grounded shields, other
ambient temperatures, circuit configurations or installation requirements.
(5) Recommended size of rigid or nonmetallic conduit for three
conductors based on 40% maximum fill.
*The jam ratio conduit l.D. to cable O.D. should be checked to avoid possible jamming.
|
|