THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 10
Okoguard®-Okoseal® Type MV-105
15kV Shielded Power Cable
One Okopact® (Compact Stranded) Aluminum Conductor/105°C Rating
100% and 133% Insulation Level
UL
A Conductor-Okopact (Compact Stranded) Aluminum

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Insulation Screen-Extruded Semiconducting EPR

E Shield-Copper Tape

F Jacket-Okoseal


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil, acids and most chemicals.

Applications
Okoguard shielded Okoseal Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits.

Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250-51, or messenger supported in industrial establishments and electric utilities.

Specifications
Conductor: Class B compact stranded aluminum per ASTM B-400.

Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Insulation Screen: Extruded semiconducting EPR insulation screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8 and UL 1072.

Shield: 5 mil bare copper tape helically applied.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682 and UL 1072 for polyvinyl chloride jackets.

UL Listed as Type MV-105 and sunlight resistant in accordance with UL 1072. CSA Listed to C68-3.

Product Features
Triple tandem extruded, all EPR system. Okoguard cables meet or exceed all recognized industry standards (UL, AEIC, NEMA/ICEA, IEEE). 105°C continuous operating temperature 140°C emergency rating. 250°C short circuit rating. Excellent corona resistance. Screens are clean stripping. Exceptional resistance to "treeing". Moisture resistant. Resistant to most oils, acids, and alkalies. Sunlight resistant. Improved Temperature Rating.


1-Catalog Number
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Approx. Dia. over Insulation(in.)
5-Approx. Dia. over Screen(in.)
6-Jacket Thickness - mils
7-Jacket Thickness - mm
8-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(1)
13-Ampacities Direct Burial(2)
14-Ampacities Underground Duct(3)
15-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Okoguard Insulation:175 mils(4.45mm), 100% Insulation Level
135-23-3011 2 33.6 0.66 0.72 80 2.03 0.91 23.0 445 495 130 175 130 3
135-23-3013 1 42.4 0.69 0.75 80 2.03 0.94 23.8 480 530 150 200 145 3
135-23-3015 1/0 53.5 0.73 0.79 80 2.03 0.97 24.7 525 620 170 230 165 3
135-23-3017 2/0 67.4 0.77 0.83 80 2.03 1.02 25.8 580 675 200 260 190 3
135-23-3019 3/0 85.0 0.82 0.89 80 2.03 1.06 27.0 640 735 225 295 215 3
135-23-3021 4/0 107.0 0.87 0.93 80 2.03 1.12 28.3 715 810 260 340 245 3
135-23-3023 250 127.0 0.91 0.97 80 2.03 1.16 29.4 780 890 290 370 270 3 1/2
135-23-3027 350 177.0 1.01 1.07 80 2.03 1.26 32.0 940 1080 350 450 330 3 1/2
135-23-3031 500 253.0 1.13 1.21 80 2.03 1.40 35.4 1180 1375 430 545 400 4
135-23-3035 750 380.0 1.31 1.39 80 2.03 1.60 40.0 1545 1815 540 680 490 5
135-23-3037 1000 507.0 1.47 1.55 110 2.79 1.80 45.6 1990 2260 640 795 565 5
Okoguard Insulation:220 mils(5.59mm), 133% Insulation Level
135-23-3111 2 33.6 0.75 0.81 80 2.03 1.00 25.3 530 625 130 175 130 3
135-23-3113 1 42.4 0.78 0.84 80 2.03 1.03 26.1 570 665 150 200 145 3
135-23-3115 1/0 53.5 0.82 0.88 80 2.03 1.06 27.0 615 710 170 230 165 3
135-23-3117 2/0 67.4 0.87 0.93 80 2.03 1.10 28.3 680 775 200 260 190 3 1/2
135-23-3119 3/0 85.0 0.91 0.97 80 2.03 1.16 29.3 740 835 225 295 215 3 1/2
135-23-3121 4/0 107.0 0.96 1.02 80 2.03 1.21 30.7 815 930 260 340 245 3 1/2
135-23-3123 250 127.0 1.01 1.08 80 2.03 1.27 32.2 910 1045 290 370 270 4
135-23-3127 350 177.0 1.11 1.18 80 2.03 1.37 34.8 1075 1215 350 450 330 4
135-23-3131 500 253.0 1.22 1.30 80 2.03 1.49 37.7 1305 1505 430 545 400 5
135-23-3135 750 380.0 1.40 1.48 110 2.79 1.73 43.9 1785 2050 540 680 490 5
135-23-3137 1000 507.0 1.56 1.66 110 2.79 1.91 48.5 2185 2605 640 795 565 6
Minimum Manufacturing Quantity for non-stock items is 5000'.

Ampacities

(1) Ampacities are in accordance with Table 310-74 of the NEC for three single Type MV-105 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 105°C.

(2) Ampacities are in accordance with Table 310-82 of the NEC for an insulated sinagle conductor directly buried with a conductor temperature rating of 105°C ambient earth temperature of 20°C, 100% Load Factor, thermal resistance (RHO) of 90. 7 1/2 inch spacing between conductor center lines, and 24 inch spacing between circuits.

(3) Ampacities are in accordance with Table 310-78 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 105°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

Refer to the NEC, IEEE/ICEA S-135 Power Cable Ampacities, or the Okonite Engineering Data Bulletin EHB for installation in duct banks, multiple point grounded shields, other ambient temperatures, circuit configurations or installation requirements.

(4) Recommended size of rigid or nonmetallic conduit for three conductors based on 40% maximum fill.

*The jam ratio, conduit I.D. to cable O.D. should be checked to avoid possible jamming.

B/97010210
BACK TO DATA SHEET INDEX

| WELCOME | WHAT'S NEW | PRODUCT OVERVIEW | PRODUCT CATALOG | EVENTS |
| SALES OFFICES | MANUFACTURING PLANTS | SERVICE CENTERS | GLOSSARY | U.S. MAP |
 | ENGINEERING TECHNICAL CENTER | SEARCH OKONITE | SURPLUS INVENTORY |
DAILY PRICES FOR COPPER, LEAD, ALUMINUM AND STEEL SHEETS

| HOMEPAGE | CONTACT US |