THE OKONITE COMPANY
COMPACT STRAND CONSTRUCTION
Product Data
Section 2: Sheet 1
Okoguard®-Okoseal® Type MV-90
2.4 kV Nonshielded Power Cable
One Okopact® (Compact Stranded) Copper Conductor
90°C Rating Wet or Dry
UL
A Uncoated, Okopact (Compact Stranded) Copper Conductor

B Strand Screen-Extruded Semiconducting EPR

C Insulation-Okoguard EPR

D Jacket-Okoseal


Insulation
Okoguard is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequalled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

Jackets
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil, acids and most chemicals.

Applications
Okoguard-Okoseal 2.4 kV cables are heavy duty nonshielded cables designed for use at up to 2.4 kV phase-to-phase in wet or dry locations in accordance with NEC Section 310.6 and Table 310.63.

Okoguard-Okoseal nonshielded cables are recommended for power distribution and motor circuits in generating plants and substations; in industrial and commercial buildings.

Single conductors may be installed in industrial or commercial occupancies in triplexed or random lay in any raceway or duct in wet or dry locations, or in open runs as permitted by NEC Articles 396.

Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.

Strand Screen: Extruded semiconducting EPR strand screen meets or exceeds electrical and physical requirements of ICEA S-96-659/NEMA WC71 and UL 1072.

Insulation: Meets or exceeds electrical and physical requirements of ICEA S-96-659/NEMA WC71,Table 310.63 of the NEC and UL 1072.

Jacket: Meets or exceeds electrical and physical requirements of ICEA S-96-659/NEMA WC71 for polyvinyl chloride jackets, UL 1072, and NEC Table 310.63.

UL Listed as Type MV-90 in accordance with UL 1072.

1/C 2.4 kV non-shielded cables can surface discharge in service when in a random phase spacing or when in contact with grounded surfaces.

Product Features

  • Okoguard cables meet or exceed all recognized industry standards
    (UL, NEMA/ICEA, IEEE).
  • 90°C continuous operating temperature.
  • 130°C emergency rating.
  • 250°C short circuit rating.
  • Excellent corona resistance.
  • Exceptional resistance to "treeing"
  • Stress cones not required.
  • Moisture resistant.
  • Resistant to most oils, acids, and alkalies.
  • Sunlight Resistant

1-Catalog Number(1)
2-Conductor Size - AWG or kcmil
3-Conductor Size - mm2
4-Insulation Thickness - mils
5-Insulation Thickness - mm
6-Jacket Thickness - mils
7-Jacket Thickness - mm
08-Approx. O.D. - Inches
09-Approx. O.D. - mm
10-Approx. Net Weight lbs./1000'
11-Approx. Ship Weight lbs./1000'
12-Ampacities Conduit in Air(2)
13-Ampacities Underground Duct(3)
14-Conduit Size-Inches*(4)
1 2 3 4 5 6 7 8 9 10 11 12 13 14
114-24-3115 8 8.4 125 3.18 80 2.01 0.60 15.1 210 240 55 64 2
114-24-3117 6 13.3 125 3.18 80 2.03 0.63 16.0 250 285 75 85 2
114-24-3119 4 21.2 125 3.18 80 2.03 0.67 17.1 320 345 97 110 2
114-24-3121 2 33.6 125 3.18 80 2.03 0.73 18.6 420 480 130 145 2
114-24-3123 1 42.4 125 3.18 80 2.03 0.76 19.4 485 545 155 170 2 1/2
114-24-3125 1/0 53.5 125 3.18 80 2.03 0.80 20.3 565 625 180 195 2 1/2
114-24-3127 2/0 67.4 125 3.18 80 2.03 0.84 21.3 670 730 205 220 2 1/2
114-24-3129 3/0 85.0 125 3.18 95 2.41 0.92 23.3 820 910 240 250 3
114-24-3131 4/0 107.0 125 3.18 95 2.41 0.97 24.5 975 1065 280 290 3
114-24-3133 250 127.0 140 3.56 110 2.79 1.08 27.4 1180 1270 315 320 3
114-24-3137 350 177.0 140 3.56 110 2.79 1.18 29.9 1535 1640 385 385 3 1/2
114-24-3143 500 253.0 140 3.56 110 2.79 1.29 32.9 2050 2175 475 470 3 1/2
114-24-3149 750 380.0 155 3.94 125 3.18 1.54 39.0 3000 3180 600 585 5
114-24-3151 1000 507.0 155 3.94 125 3.18 1.69 43.0 3855 4105 690 670 5

Minimum Manufacturing Quantity for non-stock items is 5000'

Aluminum Okopact Conductors

(1) Aluminum Okopact conductors are available on special order. To order aluminum Okopact conductors, change the first three digits of the catalog number from 114 to 134.

Ampacities

(2) Ampacities are in accordance with Table 310.73 of the NEC for three single Type MV-90 conductors, or single conductors twisted together (triplexed) and installed in an isolated conduit in air at an ambient temperature of 40°C and a conductor temperature of 90°C.

(3) Ampacities are in accordance with Table 310.77 of the NEC for three single conductors or triplexed cable in one underground raceway, three feet deep with a conductor temperature of 90°C, 100% Load Factor, an ambient earth temperature of 20°C, and thermal resistance (RHO) of 90.

(4) Recommended sizes of rigid or nonmetallic conduit for 3 conductors based on 40% maximum fill.

* The jam ratio, conduit I.D. to cable O.D., should be checked to avoid possible jamming.

E/05080201